1. Introduction & Scope

The BECSys5 is a modular building energy control system designed for HVAC, lighting, and auxiliary load management. This manual covers hardware installation, network configuration, controller addressing, and core technical parameters for system integrators and certified technicians.

Prerequisites:

6.2 Point-to-Point Verification

| Point | Procedure | Expected Result | |-------|------------|------------------| | AI | Apply 5.00V from calibrator | Read 50% of span | | DI | Short COM to DI terminal | LED on, status = Closed | | AO | Command 50% from Web UI | Output measures 5.0V ±0.05V | | DO | Enable from UI | Relay clicks, continuity across NO/COM | becsys5 installation and technical manual

8.2 Firmware Upgrade

  1. Download becsys5_fw_v5.2.3.bin from manufacturer portal.
  2. Web UI → System → Firmware Update → Upload file.
  3. Controller reboots automatically (approx. 2 minutes).
  4. Verify version on Status page.

⚠️ Do not power cycle during upgrade – risk of bricking. BECSys5 Installation and Technical Manual 1


8.1 Electrical Specifications (MCM)

| Parameter | Value | |-----------|-------| | Supply voltage | 24V DC ±20% | | Max power consumption | 60W (base) / 120W (fully loaded) | | Inrush current | <20A for 1ms | | Isolation | 1500V AC (input to ground) | BECSys5 Site Controller (firmware v5